Phoenix Surge Arrester 3P+N 40Ka

R933.72

FloatOr as low as R186.75 / month interest-free, using your existing credit card. For orders over R100.00.How it works

VAL-MS-EE-T2-3+1-320 – Type 2 surge arrester

Surge protective device, 4-channel (in 3+1 circuit), for installation on NS 35/7,5 voltage: 230 V AC
Commercial Data

7 in stock

Categories: , SKU: 2910575

Description

Item number 2910575
Packing unit 1 pc
Minimum order quantity 1 pc
Sales key CL1
Product key CLP211
GTIN 4055626462660
Weight per piece (including packing) 411 g
Weight per piece (excluding packing) 394.4 g
Customs tariff number 85363030
Country of origin CN

 

VAL-MS-EE-T2-3+1-320 – Type 2 surge arrester
Technical data
Product properties

Product type Surge arrester
IEC test classification II
T2
EN type T2
IEC power supply system TN-S, TT
Type DIN rail module, two-section, divisible
Number of positions 4
Surge protection fault message Optical

 

Insulation characteristics

Overvoltage category III
Pollution degree 2

 

Nominal frequency fN 50 Hz (60 Hz)

Electrical properties

Connection Data

Connection method Screw connection
Screw thread M5
Tightening torque 3 Nm (1.5 mm² … 16 mm²)
4.5 Nm (25 mm² … 35 mm²)
Stripping length 16 mm
Conductor cross section flexible 1.5 mm² … 25 mm²
Conductor cross section rigid 1.5 mm² … 35 mm²
Conductor cross section AWG 15 … 2
Connection method Fork-type cable lug
Conductor cross section flexible (for lugs) 1.5 mm² … 16 mm²

Dimensions

Width 71 mm
Height 90 mm
Depth 64.7 mm
Horizontal pitch 4 Div.

VAL-MS-EE-T2-3+1-320 – Type 2 surge arrester

Material specifications

Color Traffic grey B (RAL 7043)
Flammability rating according to UL 94 V-0
CTI value of material 600
Insulating material PA 6.6/PBT
Material group I
Housing material PA 6.6, PBT


Protective Circuit

Mode of protection L-N
L-PE
N-PE
Direction of action 3L-N & N-PE
Nominal voltage Un 240/415 V AC (TN-S)
240/415 V AC (TT)
Nominal frequency fN 50 Hz (60 Hz)
Maximum continuous operating voltage UC (L-N) 335 V AC
Maximum continuous operating voltage UC (L-PE) 335 V AC
Maximum continuous operating voltage UC (N-PE) 260 V AC
Rated load current IL 80 A
Residual current IPE ≤ 5 µA
Standby power consumption PC ≤ 450.00 mVA
Nominal discharge current In (8/20) µs 20 kA
Maximum discharge current Imax (8/20) µs 40 kA
Follow current interrupt rating Ifi (N-PE) 100 A
Short-circuit current rating ISCCR 25 kA
Voltage protection level Up (L-N) ≤ 1.6 kV
Voltage protection level Up (L-PE) ≤ 1.9 kV
Voltage protection level Up (N-PE) ≤ 1.5 kV
Residual voltage Ures (L-N) ≤ 1.6 kV (at In )
≤ 1.5 kV (at 10 kA)
≤ 1.3 kV (at 5 kA)
≤ 1.1 kV (at 3 kA)
Residual voltage Ures (L-PE) ≤ 1.9 kV (at In )
≤ 1.5 kV (at 10 kA)
≤ 1.3 kV (at 5 kA)
≤ 1.2 kV (at 3 kA)
Residual voltage Ures (N-PE) ≤ 0.4 kV (at In )
≤ 0.25 kV (at 10 kA)
≤ 0.15 kV (at 5 kA)
≤ 0.1 kV (at 3 kA)
TOV behavior at UT (L-N) 415 V AC (5 s / withstand mode)

 

VAL-MS-EE-T2-3+1-320 – Type 2 surge arrester

440 V AC (120 min / safe failure mode)
TOV behavior at UT (N-PE) 1200 V AC (200 ms / withstand mode)
Response time tA (L-N) ≤ 25 ns
Response time tA (L-PE) ≤ 100 ns
Response time tA (N-PE) ≤ 100 ns
Max. backup fuse with V-type through wiring 80 A (gG)
Max. backup fuse with branch wiring 125 A (gG)

 

Environmental and real-life conditions
Ambient Conditions

Degree of protection IP20 (only when all terminal points are used)
Ambient temperature (operation) -40 °C … 80 °C
Ambient temperature (storage/transport) -40 °C … 80 °C
Altitude ≤ 2000 m (amsl)
Permissible humidity (operation) 5 % … 95 %
Shock (operation) 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation) 5g (10 … 500 Hz / 2.5 h / X, Y, Z)

 

Standards and regulations

Standards/specifications IEC 61643-11
Note 2011
Standards/specifications EN 61643-11
Note 2012

 

Mounting

Mounting type DIN rail: 35 mm


VAL-MS-EE-T2-3+1-320 – Type 2 surge arrester

ECLASS

ECLASS-11.0 27130805
ECLASS-13.0 27171202

 

ETIM

ETIM 8.0 EC000941

 

UNSPSC

UNSPSC 21.0 39121600

 

                               VAL-MS-EE-T2-3+1-320 – Type 2 surge arrester
Environmental product compliance
EU RoHS

Fulfills EU RoHS substance requirements Yes, No exemptions

 

China RoHS

Environment friendly use period (EFUP) EFUP-E
No hazardous substances above the limits

EU REACH SVHC

REACH candidate substance (CAS No.) No substance above 0.1 wt%

 

VAL-MS-EE-T2-3+1-320 – Type 2 surge arrester

Accessories
MPB 18/4- 8 – Wiring bridge
Wiring bridge for modules with connecting pitch 17.5 mm, 4-phase, 8-pos.

MPB 18/4-12 – Wiring bridge

Wiring bridge for modules with connecting pitch 17.5 mm, 4-phase, 12-pos.

VAL-MS-EE-T2-3+1-320 – Type 2 surge arrester

ZBN 18:UNBEDRUCKT – Zack marker strip
Zack marker strip, Strip, white, unlabeled, can be labeled with: CMS-P1- PLOTTER, PLOTMARK, mounting type: snapped, for terminal block width: 18 mm, lettering field size: 18 x 5 mm, Number of individual labels: 5

ZBN 18,LGS:ERDE – Marker for terminal blocks
Marker for terminal blocks, Strip, white, labeled, horizontal: Grounding symbol, mounting type: snapped, for terminal block width: 18 mm, lettering field size: 18 x 5 mm, Number of individual labels: 5

VAL-MS-EE-T2-3+1-320 – Type 2 surge arrester

ZBN 18,LGS:L1-N,ERDE – Marker for terminal blocks
Marker for terminal blocks, Strip, white, labeled, horizontal: L1, L2, L3, N, GND, mounting type: snapped, for terminal block width: 18 mm, lettering field size: 18 x 5 mm, Number of individual labels: 5

B-STIFT – Marker pen
Marker pen, for manual labeling of unprinted Zack strips, smear-proof and waterproof, line thickness 0.5 mm
VAL-MS-EE-T2-3+1-320 – Type 2 surge arrester
SZK PZ2 VDE – Screwdriver
Screwdriver, PZ crosshead, VDE insulated, size: PZ 2 x 100 mm, 2-component grip, with non-slip grip

VAL-MS-EE-T2-320-P – Type 2 surge protection plug
Surge protection connector type 2 with high-capacity varistor for VAL-MS base element, thermal monitoring, visual fault warning. Design: 320 V AC

Additional information

Weight 0.322 kg
Dimensions 4.57 × 0.75 × 0.52 cm