R1,688.69

trip unit TM125D for ComPacT NSX
160/250 circuit breakers. thermal
magnetic. rating 125 A. 3 poles 3d

Pay over 3 EQUAL zero-interest instalments of R562.90 with PayJustNow.
Find out how...

HOW IT WORKS

PayJustNow allows you to pay for your purchase over 3 payments with 0% interest and no fees. Pay a third at checkout and receive your goods immediately. The remaining two instalments are debited on your selected instalment dates.

Browse online or in-store and proceed to checkout

Choose PayJustNow as your payment method

Create your account and receive an instant approval decision

Complete your transaction

WHAT YOU WILL NEED

Be over 18 years old

Be a South African resident

Have a debit or credit card

Have a valid email address

0% INTEREST. 3 PAYMENTS. NO STRESS.

WHY PAY ANY OTHER WAY?

1 in stock

Or as low as R337.74 over 5 months interest free, using your credit card. For orders over R0.01.How it works
Categories: , SKU: C163TM125 Brand:

Description

Main
Range ComPacT new generation
Range of product ComPacT NSX100…250 new generation
Product or component type Trip unit
Trip unit name TM-D
Trip unit technology Thermal-magnetic
Range compatibility ComPacT new generation NSX160
ComPacT new generation NSX250
Device application Distribution
Poles description 3P
Protected poles description 3D
Trip unit protection functions LI
Protection type L : for overload protection (thermal)
I : for short-circuit protection (magnetic)
Trip unit rating 125 A at 40 °C
[Ue] rated operational voltage 690 V AC 50/60 Hz
network type AC
Network frequency 50/60 Hz
Circuit breaker mounting mode Fixed

Complementary
Long-time pick-up adjustment
type Ir (thermal protection)
Adjustable
[Ir] long-time protection pick-up
adjustment range
0.7…1 x In
Long-time protection delay
adjustment type tr
Fixed
[tr] long-time protection delay
adjustment range
120…400 s at 1.5 x In
15 s at 6 x Ir
Instantaneous protection pick-up
adjustment type Ii
Fixed
[Ii] instantaneous protection pickup
adjustment range
1250 A
Earth-leakage protection Without

Environment
Standards EN/IEC 60947-2
Electrical shock protection class Class II

Pollution degree 3 conforming to IEC 60947-1
IP degree of protection IP40 conforming to IEC 60529
Ambient air temperature for
operation
-25…70 °C
Ambient air temperature for
storage
-50…85 °C