Description
Main
Device application Distribution
Range Acti9
Product name Acti9 iC60
Product or component type Miniature circuit-breaker
Device short name iC60a
Poles description 4P
Number of protected poles 4
[In] rated current 63 A
Network type AC
Trip unit technology Thermal-magnetic
Curve code C
Breaking capacity 4500 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
10 KA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 KA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
Utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2
Suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2
Standards EN 60898-1
EN 60947-2
IEC 60947-2
IEC 60898-1
Complementary
Network frequency 50/60 Hz
Magnetic tripping limit 8 x In +/- 20 %
[Ics] rated service breaking capacity 10 KA 100 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
6 KA 100 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
10 KA 100 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
6 KA 100 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
4500 A 100 % conforming to EN 60898-1 – 400 V AC 50/60 Hz
4500 A 100 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
Limitation class 3 conforming to EN 60898-1
[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 6 KV conforming to EN 60947-2
6 KV conforming to IEC 60947-2
Contact position indicator Yes
Control type Toggle
Local signalling Trip indicator
Mounting mode Removable comb busbar installed
Mounting support DIN rail
9 mm pitches 8
Width 72 Mm
Colour White
Connections – terminals Single terminal (top or bottom) 1…35 mm2 rigid
Single terminal (top or bottom) 1…25 mm2 flexible
Wire stripping length 14 Mm for top or bottom connection
Tightening torque 3.5 N.M top or bottom
Earth-leakage protection Separate block
Environment
IP degree of protection IP20 B conforming to EN/IEC 60529
Pollution degree 3 conforming to EN 60947-2
3 conforming to IEC 60947-2
Overvoltage category II
Tropicalisation 2 conforming to EN/IEC 60068-2-78
Relative humidity 95 %
Operating altitude 0…2000 m
Ambient air temperature for operation -35…70 °C
Ambient air temperature for storage -40…85 °C