Description
Main
Range ComPacT
Product name ComPacT NSX
Device short name NSX100F
Product or component type Circuit breaker
Device application Distribution
Poles description 3P
Protected poles description 3D
[In] rated current 63 A at 40 °C
[Ue] rated operational voltage 690 V AC 50/60 Hz
Network type AC
Network frequency 50/60 Hz
Suitability for isolation Yes conforming to EN/IEC 60947-2
Utilisation category Category A
Breaking capacity 85 KA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
36 KA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
35 KA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 KA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
22 KA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
8 KA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
85 KA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1
25 KA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1
10 KA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Breaking capacity code F 36 kA 415 V AC
Trip unit name TM-D
Trip unit technology Thermal-magnetic
Trip unit protection functions LI
Control type Toggle
Mounting mode Fixed
Complementary
[Ui] rated insulation voltage 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 8 KV
[Ics] rated service breaking capacity 85 KA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
36 KA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
35 KA at 440 V AC 50/60 Hz conforming to IEC 60947-2
12 KA at 500 V AC 50/60 Hz conforming to IEC 60947-2
11 KA at 525 V AC 50/60 Hz conforming to IEC 60947-2
4 KA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability 50000 Cycles
Electrical durability 50000 Cycles at 440 V In/2
30000 Cycles at 440 V In
20000 Cycles at 690 V In/2
10000 Cycles at 690 V In
Power dissipation per pole 8.61 W
Mounting support Backplate
Mounting position Horizontal and vertical
Flat on the back
Upside connection Front
Downside connection Front
Connection pitch 35 Mm
Protection type L : for overload protection (thermal)
I : for short-circuit protection (magnetic)
Trip unit rating 63 A at 40 °C
Long time pick-up adjustment type Ir Adjustable
Long time pick-up adjustment range 0.7…1 x In
Long time delay adjustment type Fixed
[tr] long-time delay adjustment range 120…400 S at 1.5 x In
15 S at 6 x Ir
Instantaneous pick-up adjustment type Ii Fixed
Instantaneous pick-up adjustment range 500 A
Earth-leakage protection Without
Number of slots 5 slot(s)
Width 105 Mm
Height 161 Mm
Depth 86 Mm
Net weight 2.05 Kg
Environment
Standards EN/IEC 60947-2
Overvoltage category Class II
Electrical shock protection class Class II
Pollution degree 3 conforming to IEC 60664-1
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to IEC 62262
Ambient air temperature for operation -25…70 °C
Ambient air temperature for storage -50…85 °C
Relative humidity 0…95 %
Operating altitude 0…2000 m without derating
2000 m…5000 m with derating