Description
Main
| Range of product | EasyPact |
| Product or component type | Circuit breaker |
| Device short name | Easypact EZC250N |
| Circuit breaker name | Easypact EZC250N |
| Device application | Distribution |
| Poles description | 3P |
| Protected poles description | 3t |
| Network type | DC
AC |
| Network frequency
|
50/60 Hz |
| [In] rated current | 150 A at 40 °C |
|
[Ui] rated insulation voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 KV conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2 |
| Breaking capacity code | N |
| Breaking capacity | 20 KA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 KA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2 50 KA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 20 KA Icu at 125 V DC 1P conforming to IEC 60947-2 20 KA Icu at 250 V DC 2P conforming to IEC 60947-2 25 KA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 KA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2 8 KA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service breaking capacity | 10 KA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 KA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 10 KA at 125 V DC conforming to IEC 60947-2 10 KA at 250 V DC conforming to IEC 60947-2 25 KA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 4 KA at 550 V AC 50/60 Hz conforming to IEC 60947-2 12.5 KA at 380 V AC 50/60 Hz conforming to IEC 60947-2 12.5 KA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 |
| Suitability for isolation | Yes conforming to IEC 60947-2 |
|
Utilisation category |
Category A |
| Trip unit name | TM-D |
| Trip unit technology | Thermal-magnetic |
| Trip unit rating | 150 A at 50 °C |
| Protection type | Short-circuit protection
Overload protection |
| Pollution degree | 3 conforming to IEC 60664-1
3 conforming to IEC 947-1 |
Complementary
| Control type | Toggle |
| Mounting mode | Fixed |
| Mounting support | Backplate |
| Upside connection | Front |
| Downside connection | Front |
| Mechanical durability | 10000 Cycles |
| Electrical durability | Category A: 5000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2 |
| Connection pitch | 35 Mm |
| Local signalling | Positive contact indication |
| Neutral protection setting | Without protection |
| Earth-leakage protection | Without |
| Height | 165 Mm |
| Width | 105 Mm |
| Depth | 60 Mm |
Environment
| Standards | GB/T 14048.2
EN/IEC 60947-1 EN/IEC 60947-2 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to IEC 62262 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -35…85 °C |
Packing Units
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 10.900 Cm |
| Package 1 Width | 11.600 Cm |
| Package 1 Length
|
18.100 Cm |
| Package 1 Weight | 1.587 Kg |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 8 |
| Package 2 Height | 30.000 Cm |
| Package 2 Width | 30.000 Cm |
| Package 2 Length | 40.000 Cm |
| Package 2 Weight | 13.607 Kg |
| Unit Type of Package 3 | P12 |
| Number of Units in Package 3 | 64 |
| Package 3 Height | 50.000 Cm |
| Package 3 Width | 80.000 Cm |
| Package 3 Length | 120.000 Cm |
| Package 3 Weight | 120.856 Kg |