Description
Main
Range of product
|
EasyPact |
Product or component type | Circuit breaker |
Device short name | Easypact EZC250N |
Circuit breaker name | Easypact EZC250N |
Device application | Distribution |
Poles description | 3P |
Protected poles description | 3t |
Network type | AC
DC |
Network frequency | 50/60 Hz |
[In] rated current | 175 A at 40 °C |
[Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 6 KV conforming to IEC 60947-2 |
[Ue] rated operational voltage | 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2 |
Breaking capacity code | N |
Breaking capacity | 20 KA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 KA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2 50 KA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 20 KA Icu at 125 V DC 1P conforming to IEC 60947-2 20 KA Icu at 250 V DC 2P conforming to IEC 60947-2 25 KA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 KA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2 8 KA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ics] rated service breaking capacity | 10 KA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 KA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 10 KA at 125 V DC conforming to IEC 60947-2 10 KA at 250 V DC conforming to IEC 60947-2 25 KA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 4 KA at 550 V AC 50/60 Hz conforming to IEC 60947-2 12.5 KA at 380 V AC 50/60 Hz conforming to IEC 60947-2 12.5 KA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 |
Suitability for isolation | Yes conforming to IEC 60947-2 |
Utilisation category | Category A |
Trip unit name | TM-D |
Trip unit technology | Thermal-magnetic |
Trip unit rating | 175 A at 50 °C |
Protection type
|
Overload protection
Short-circuit protection
|
Pollution degree
|
3 conforming to IEC 60664-1
3 conforming to IEC 947-1
|
Complementary
Control type | Toggle |
Mounting mode | Fixed |
Mounting support | Backplate |
Upside connection | Front |
Downside connection | Front |
Mechanical durability | 10000 Cycles |
Electrical durability | Category A: 5000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
|
Connection pitch | 35 Mm |
Local signalling | Positive contact indication |
Neutral protection setting
Earth-leakage protection |
Without protection
Without |
Height | 165 Mm |
Width | 105 Mm |
Depth | 60 Mm |
Environment
Standards | EN/IEC 60947-2
GB/T 14048.2 EN/IEC 60947-1 |
IP degree of protection | IP20 conforming to IEC 60529 |
IK degree of protection | IK07 conforming to IEC 62262 |
Ambient air temperature for operation | -25…70 °C |
Ambient air temperature for storage | -35…85 °C |
Packing Units
Unit Type of Package 1
Package 1 Length 18 Cm |
PCE |
Number of Units in Package | 1 |
Package 1 Height | 11 Cm |
Package 1 With | 11.5 Cm
|
Package 1 Length | 18 Cm |
Package 1 Weight | 1.57 Kg |
Unit Type of Package 2 | S03 |
Number of Units in Package 2 | 8 |
Package 2 Height | 30 Cm |
Package 2 Weight 13 Kg | 30 Cm |
Package 2 Length | 40 Cm |
Package 2 Weight | 13 Kg |