EASYPACT TVS CONTACTOR 3P 3NO 160A 240VAC COIL

R2,798.30

EasyPact TVS contactor 3P(3 NO) –
AC-3 – <= 440 V 160A – 240 V AC
coil

Pay in 3 or 12. The Clever Way to Pay.
From over 12 months or 3 interest free payments.
Learn more...

Your flexible payment provider.

Example payment for

x 3
0% interest, zero fees.
Pay in 3
x 12
28.25% interest, plus fees.
Total Payment
Pay in 12

How does PayJustNow work?

  • Shop and choose PayJustNow at checkout.
  • Sign up and get instant approval.
  • Pay in 3 or 12.

You can complete sign-up in under 2 minutes - no need to leave your cart!

1 in stock

Or as low as R559.67 over 5 months interest free, using your credit card. For orders over R1.00.How it works
Category: SKU: LC1E160U5 Brand:

Description

Main
Range Easy TeSys
Range of product Easy TeSys Control
Product or component type Contactor
Device short name LC1E
Contactor application Motor control
Resistive load
Utilisation category AC-3
AC-3e
AC-1
Poles description 3P
[Ue] rated operational voltage Power circuit: <= 690 V AC 50/60 Hz
[Ie] rated operational current 160 A (at <55 °C) at <= 440 V AC AC-3 for power circuit
100 A (at <55 °C) at <= 440 V AC AC-3e for power circuit
200 A (at <40 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage 240 V AC 50 Hz

Complementary
Motor power kW 45 kW at 220…230 V AC 50/60 Hz
75 kW at 380…400 V
80 kW at 415 V
80 kW at 440 V
90 kW at 500 V
100 kW at 660…690 V
Pole contact composition 3 NO
[Ith] conventional free air thermal
current
200 A (at 40 °C) for power circuit
Irms rated making capacity 1600 A at 440 V AC for power circuit conforming to IEC 60947-4-1
Rated breaking capacity 1280 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand
current
1400 A 40 °C – 10 s for power circuit
Associated fuse rating 10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC
60947-5-1
315 A gG at <= 690 V coordination type 1 for power circuit
Average impedance 0.6 mOhm – Ith 200 A 50 Hz for power circuit
Power dissipation per pole 24 W AC-1
15 W AC-3
[Ui] rated insulation voltage 690 V conforming to IEC 60947-4-1
overvoltage category III
pollution degree 3

[Uimp] rated impulse withstand
voltage
8 kV coil not connected to the power circuit conforming to IEC 60947
Mechanical durability 4000000 cycles
Electrical durability 800000 cycles AC-3
250000 cycles AC-1
Control circuit type AC at 50 Hz
Control circuit voltage limits 0.85…1.1 Uc (-5…55 °C):operational 50 Hz
0.35…0.55 Uc (-5…55 °C):drop-out 50 Hz
Inrush power in VA 300 VA 50 Hz cos phi 0.9 (at 20 °C)
300 VA 60 Hz cos phi 0.9 (at 20 °C)
Hold-in power consumption in VA 22 VA 50 Hz cos phi 0.9 (at 20 °C)
22 VA 60 Hz cos phi 0.9 (at 20 °C)
Heat dissipation 3…8 W for control circuit
Operating time 20…50 ms on closing
6…20 ms on opening
Maximum operating rate 1200 cyc/h 55 °C
Connections – terminals Control circuit: screw clamp terminals 2 1…2.5 mm² – cable stiffness: flexible with
cable end
Power circuit: screw clamp terminals 1 10…120 mm² – cable stiffness: flexible with
cable end
Power circuit: screw clamp terminals 1 10…120 mm² – cable stiffness: solid without
cable end
Control circuit: screw clamp terminals 1 1…2.5 mm² – cable stiffness: flexible without
cable end
Control circuit: screw clamp terminals 2 1…2.5 mm² – cable stiffness: flexible without
cable end
Control circuit: screw clamp terminals 1 1…2.5 mm² – cable stiffness: flexible with
cable end
Control circuit: screw clamp terminals 1 1…2.5 mm² – cable stiffness: solid without
cable end
Control circuit: screw clamp terminals 2 1…2.5 mm² – cable stiffness: solid without
cable end
Power circuit: screw clamp terminals 2 10…120 mm² – cable stiffness: flexible with
cable end
Power circuit: screw clamp terminals 2 10…120 mm² – cable stiffness: solid without
cable end
Tightening torque Power circuit: 12 N.m
Control circuit: 1.2 N.m
Auxiliary contact composition 1 NO + 1 NC
Minimum switching voltage 17 V for control circuit

Minimum switching current 5 mA for control circuit
Insulation resistance > 10 MOhm for control circuit
Non-overlap time 1.5 ms on energisation guaranteed between NC and NO contact
1.5 ms on de-energisation guaranteed between NC and NO contact
Mounting support Plate
DIN rail
Environment
Standards IEC 60947-5-1
IEC 60947-4-1
IEC 60947-1
Product certifications EAC
CE
IP degree of protection IP2X conforming to IEC 60529
Protective treatment TH (pollution degree 3) conforming to IEC 60068-2-30 test Db

Permissible ambient air
temperature around the device
-20…70 °C at Uc
-60…80 °C storage
-5…55 °C operation
Operating altitude 3000 m without derating
Fire resistance 850 °C conforming to IEC 60695-2-1
Mechanical robustness Vibrations contactor open (1.5 Gn, 5…300 Hz)
Vibrations contactor closed (3 Gn, 5…300 Hz)
Shocks contactor open (6 Gn for 11 ms)
Shocks contactor closed (7 Gn for 11 ms)
Height 158 mm
Width 120 mm
Depth 132 mm
Net weight 2.3 kg