Description
Main
Range of product Harmony Electromechanical Relays
Series name RXM series
Product or component type Plug-in relay
Relay type Miniature relay
Contacts type and composition 4 C/O
Status LED With
Control type Lockable test button
[Uc] control circuit voltage 12 V DC
[Ithe] conventional enclosed thermal current 6 A
Continuous output current 5 A
Complementary
[Uimp] rated impulse withstand voltage 2.5 KV during 1.2/50 μs
[Ie] rated operational current 3 A at 28 V (DC) NC conforming to IEC
3 A at 250 V (AC) NC conforming to IEC
6 A at 28 V (DC) NO conforming to IEC
6 A at 250 V (AC) NO conforming to IEC
6 A at 277 V (AC) conforming to UL
8 A at 30 V (DC) conforming to UL
Minimum switching capacity 170 mW at 10 mA, 17 V
Electrical durability 100000 Cycles for resistive load
Rated operational voltage limits 9.6…13.2 V DC
[Ui] rated insulation voltage 250 V conforming to IEC
300 V conforming to CSA
300 V conforming to UL
Maximum switching voltage 250 V conforming to IEC
Drop-out voltage threshold >= 0.1 Uc
Load current 6 A at 250 V AC
6 A at 28 V DC
Operating time 20 ms
Maximum switching capacity 1500 VA/168 W
Average resistance 160 Ohm at 20 °C +/- 10 %
Average coil consumption 0.9 W
Mechanical durability 10000000 Cycles
Safety reliability data B10d = 100000
Operating rate <= 1200 cycles/hour under load
<= 18000 cycles/hour no-load
Utilisation coefficient 20 %
CAD overall height 79 Mm
CAD overall depth 78.45 Mm
Reset time 20 Ms
Dielectric strength 1300 V AC between contacts with micro disconnection
2000 V AC between coil and contact with basic insulation
2000 V AC between poles with basic insulation
Compatibility code RXM
Protection category RT I
Pollution degree 2
Operating position Any position
Test levels Level A group mounting
Device presentation Complete product
Contacts material AgNi
Shape of pin Flat (faston type)
Net weight 0.037 Kg
Environment
Ambient air temperature for operation -40…55 °C
IP degree of protection IP40 conforming to IEC 60529
Standards CSA C22.2 No 14
IEC 61810-1
UL 508
Product certifications UL[RETURN]Lloyd’s[RETURN]CE[RETURN]CSA[RETURN]GOST[RETURN]IE-
CEE CB Scheme
Ambient air temperature for storage -40…85 °C
Vibration resistance 3 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles in operation
5 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles not operating
Shock resistance 10 gn for in operation
30 gn for not operating