Description
Main
Range of product Harmony Electromechanical Relays
Series name Miniature
Product or component type Plug-in relay
Device short name RXM
[Uc] control circuit voltage 120 V AC 50/60 Hz
Contacts type and composition 2 C/O
Status LED With
Control type Lockable test button
Continuous output current 10 A
Complementary
[Uimp] rated impulse withstand
voltage
4 kV during 1.2/50 µs
[Ie] rated operational current 12 A at 28 V (DC) NO conforming to IEC
12 A at 250 V (AC) NO conforming to IEC
6 A at 28 V (DC) NC conforming to IEC
6 A at 250 V (AC) NC conforming to IEC
12 A at 28 V (DC) conforming to UL
12 A at 277 V (AC) conforming to UL
Minimum switching capacity 170 mW at 10 mA, 17 V
Electrical durability 100000 cycles for resistive load
Average coil consumption in VA 1.2 at 60 Hz
Rated operational voltage limits 96…132 V AC
[Ui] rated insulation voltage 250 V conforming to IEC
300 V conforming to CSA
300 V conforming to UL
Average consumption 1.2 VA at 60 Hz
Maximum switching voltage 250 V conforming to IEC
Drop-out voltage threshold >= 0.15 Uc
Load current 12 A at 250 V AC
12 A at 28 V DC
Operating time 20 ms
Maximum switching capacity 3000 VA/336 W
Average resistance 4430 Ohm at 20 °C +/- 15 %
Mechanical durability 10000000 cycles
Safety reliability data B10d = 100000
Operating rate <= 1200 cycles/hour under load
<= 18000 cycles/hour no-load
Utilisation coefficient 20 %
CAD overall height 79 mm
CAD overall depth 78.45 mm
reset time 20 ms
Dielectric strength 1300 V AC between contacts with micro disconnection
2000 V AC between coil and contact with basic insulation
2000 V AC between poles with basic insulation
Compatibility code RXM
Protection category RT I
pollution degree 3
Operating position Any position
Test levels Level A group mounting
Device presentation Complete product
Contacts material AgNi
Shape of pin Flat
Net weight 0.037 kg
Environment
Ambient air temperature for
operation
-40…55 °C
IP degree of protection IP40 conforming to IEC 60529
Standards CSA C22.2 No 14
IEC 61810-1
UL 508
Product certifications UL
Lloyd’s
CE
CSA
GOST
IECEE CB Scheme
Ambient air temperature for
storage
-40…85 °C
Vibration resistance 3 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles in operation
5 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles not operating
Shock resistance 10 gn for in operation
30 gn for not operating