Description
Main
Range of product Harmony Electromechanical Relays
Series name Miniature
Product or component type Pre-assembled plug-in relay with socket
Device short name RXM
[Uc] control circuit voltage 24 V DC
Contacts type and composition 2 C/O
Status LED With
Control type Lockable test button
Continuous output current 10 A
Complementary
[Uimp] rated impulse withstand
voltage
4 kV during 1.2/50 µs
[Ie] rated operational current 6 A at 28 V (DC) NC conforming to IEC
6 A at 250 V (AC) NC conforming to IEC
10 A at 28 V (DC) NO conforming to UL
10 A at 250 V (AC) NO conforming to UL
minimum switching current 10 mA
Minimum switching voltage 17 V
Minimum switching capacity 170 mW at 10 mA, 17 V
Electrical durability 100000 cycles for resistive load
Rated operational voltage limits 19.2…26.4 V DC
[Ui] rated insulation voltage 250 V conforming to IEC
Maximum switching voltage 250 V
Drop-out voltage threshold >= 0.1 Uc DC
Load current 10 A at 250 V AC
10 A at 28 V DC
Operating time 20 ms
Maximum switching capacity 2500 VA AC
280 W DC
Average resistance 650 Ohm at 20 °C +/- 10 %
Average coil consumption 0.9 W, DC
Mechanical durability 10000000 cycles
Safety reliability data B10d = 100000
Operating rate <= 1200 cycles/hour under load
<= 18000 cycles/hour no-load
Utilisation coefficient 20 %
CAD overall width 26.9 mm
CAD overall height 79 mm
CAD overall depth 78.45 mm
torque value 1 N.m
reset time 20 ms
Connections – terminals Connector, 1 x 0.25…1 x 2.5 mm² (AWG 22…AWG 14) flexible with cable end
Connector, 2 x 0.25…2 x 1 mm² (AWG 22…AWG 17) flexible with cable end
Connector, 1 x 0.5…1 x 2.5 mm² (AWG 20…AWG 14) solid without cable end
Connector, 2 x 0.5…2 x 1.5 mm² (AWG 20…AWG 16) solid without cable end
Dielectric strength 1300 V AC between contacts with micro disconnection
2000 V AC between coil and contact with basic insulation
2000 V AC between poles with basic insulation
Compatibility code RXM
Protection category RT I
pollution degree 2
Operating position Any position
Test levels Level A group mounting
Device presentation Complete product
Sale per indivisible quantity 30
Contacts material AgNi
Net weight 0.096 kg
Environment
Ambient air temperature for
operation
-40…55 °C
IP degree of protection IP20 conforming to IEC 60529
Standards UL 508
IEC 61810-1
CSA C22.2 No 14
IEC 61984
Product certifications UL
Lloyd’s
CE
CSA
GOST
IECEE CB Scheme
Ambient air temperature for
storage
-40…85 °C
Vibration resistance 3 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles in operation
5 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles not operating
Shock resistance 10 gn for in operation
30 gn for not operating