Description
TEST RESULTS OF TYPE TESTS PERFORMED ON JOINTMASTER LOW VOLTAGE RESIN KITS TO BS6910
| TEST | REQUIREMENT | RESULTS |
| Initial Insulation Resistance | > 50 MW | Complied |
| Initial Voltage Withstand (2kV/15min | No Breakdown | Complied |
| Impact Test | No Cracks or damage | Complied |
| Insulation Resistance Me After impact test | > 50 MVV | Complied |
| Voltage Withstand after impact test 2kV/15min | No Breakdown | Complied |
| Load Cycling Test 100 cycles @ 85C | No Breakdown | Complied |