LIMIT SWITCH MET STEEL ROLL PLUNGE

R1,591.85

Limit switch, Limit switches XC Standard, XCKM, steel roller plunger, 1NC+1 NO, snap action, M20

Pay over 3 EQUAL zero-interest instalments of R530.62 with PayJustNow.
Find out how...

HOW IT WORKS

PayJustNow allows you to pay for your purchase over 3 payments with 0% interest and no fees. Pay a third at checkout and you get your goods as if you have paid in full. The remaining two instalments are debited on your specified instalment date.

Browse online or in-store and proceed to check-out

Choose PayJustNow as your payment method

Create your account and get an instant approval decision

Complete your transaction

WHAT YOU WILL NEED

BE OVER 18
YEARS OLD

BE AN SA
RESIDENT

HAVE A DEBIT OR
CREDIT CARD

HAVE A VALID
EMAIL ADDRESS

0% INTEREST. 3 PAYMENTS. NO STRESS.

WHY PAY ANY OTHER WAY?

Categories: , SKU: XCKM102H29

Description

Main
Range of product Telemecanique Limit switches XC Standard
Series name Standard format
Product or component
type

Limit switch
Device short name XCKM
Body type Fixed
Head type Plunger head
Material Metal
Body material Zamak
Fixing mode By the body
Movement of operating
head

Linear

Type of operator Spring return roller plunger metal
Type of approach Lateral approach, 2 directions
Cable entry 3 entries tapped for M20 x 1.5 cable gland, cable

outer diameter: 7…13 mm

Number of poles 2
Contacts type and
composition

1 NC + 1 NO
Contact operation Snap action

Complementary
Switch actuation By 30° cam
Electrical connection Screw-clamp terminals, clamping capacity: 1 x 0.34…2 x 1.5 mm2
Contacts insulation form Zb
Number of steps 1
Positive opening With
Positive opening minimum force 36 N
Minimum force for tripping 12 N
Minimum actuation speed 0.01 m/min
Maximum actuation speed 0.5 m/s
Contact code designation A300, AC-15 (Ue = 240 V), Ie = 3 A conforming to IEC 60947-5-1 appendix A
Q300, DC-13 (Ue = 250 V), Ie = 0.27 A conforming to IEC 60947-5-1 appendix A

[Ithe] conventional enclosed thermal current 10 A AC
[Ui] rated insulation voltage 300 V conforming to UL 508

500 V (pollution degree 3) conforming to IEC 60947-1
300 V conforming to CSA C22.2 No 14
Maximum resistance across terminals 25 MOhm conforming to IEC 60255-7 category 3
[Uimp] rated impulse withstand voltage 6 KV conforming to IEC 60664
6 kV conforming to IEC 60947-1
Short-circuit protection 10 A cartridge fuse, type gG
Electrical durability 5000000 Cycles, DC-13, inductive load type, 120 V, 4 W, operating rate <60 cyc/

mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
5000000 Cycles, DC-13, inductive load type, 24 V, 7 W, operating rate <60 cyc/
mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
5000000 cycles, DC-13, inductive load type, 48 V, 10 W, operating rate <60 cyc/
mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C

Mechanical durability 20000000 cycles
Width 64 mm
Height 64 mm

Depth 30 mm
Net weight 0.255 kg
Terminals description ISO n°1 (13-14)NO
(21-22)NC

Environment
Shock resistance 50 gn for 11 ms conforming to IEC 60068-2-27
Vibration resistance 25 gn (f= 10…500 Hz) conforming to IEC 60068-2-6
IP degree of protection IP66 conforming to IEC 60529
IK degree of protection IK05 conforming to IEC 62262
Electrical shock protection class Class I conforming to IEC 61140
Class I conforming to NF C 20-030

Ambient air temperature for operation -25…70 °C
Ambient air temperature for storage -40…70 °C
Protective treatment TC
Product certifications CSA[RETURN]UL[RETURN]CCC
Standards UL 508
CSA C22.2 No 14
IEC 60204-1
IEC 60947-5-1
IEC 60204-1
IEC 60947-5-1