Main
Device application | Distribution |
Range | Acti9 |
Product name | Acti9 iC60 |
Product or component type | Miniature circuit-breaker |
Device short name | iC60a |
Poles description | 1P |
Number of protected poles | 1 |
[In] rated current | 1 A |
Network type | AC |
Trip unit technology | Thermal-magnetic |
Curve code | C |
Breaking capacity | 4500 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
6 KA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
Utilisation category | Category A conforming to EN 60947-2 Category A conforming to IEC 60947-2 |
Suitability for isolation | Yes conforming to EN 60898-1
Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
Standards | EN 60947-2
EN 60898-1 IEC 60898-1 IEC 60947-2 |
Complementary
Network frequency | 50/60 Hz |
Magnetic tripping limit | 8 x In +/- 20% |
[Ics] rated service breaking capacity | 6 KA 100 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
6 KA 100 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz 4500 A 100% conforming to EN 60898-1 – 230 V AC 50/60 Hz 4500 A 100 % conforming to IEC 60898-1 – 230 V AC 50/60 Hz
|
Limitation class | 3 conforming to EN 60898-1 3 conforming to IEC 60898-1 |
[Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 6 KV conforming to EN 60947-2
6 KV conforming to IEC 60947-2 |
Contact Position Indicator | Yes |
Control Type | Toggle |
Local Signalling | Trip Indicator |
Mounting Mode | Removable Comb Busbar Installed |
Mounting Support | DIN Rail |
9 mm Pitches | 2 |
Width | 18 mm |
Colour | White |
Connections – Terminals | Single Terminal (Top or Bottom) 1…25 mm² Rigid Single terminal (top or bottom) 1…16 mm² flexible |
Wire Stripping Length | 14 mm for Top or Bottom Connection |
Tightening Torque | 2 N·m for Top or Bottom |
Earth-Leakage Protection | Without |
Environment
IP degree of protection | IP20 B conforming to EN/IEC 60529 |
Pollution degree | 3 conforming to EN 60947-2
3 conforming to IEC 60947-2 |
Overvoltage category | II |
Tropicalisation | 2 conforming to EN/IEC 60068-2-78 |
Relative humidity | 95 % |
Operating altitude | 0…2000 m |
Ambient air temperature for operation | -35…70 °C |
Ambient air temperature for storage | -40…85 °C |
Packing Units
Unit Type of Package 1 | PCE |
Number of Units in Package 1 | 1 |
Package 1 Height | 1.8 Cm |
Package 1 Width | 7.5 Cm |
Package 1 Length | 9.5 Cm |
Package 1 Weight | 118.089 G |
Unit Type of Package 2 | BB1 |
Number of Units in Package 2 | 12 |
Package 2 Height | 8.2 Cm |
Package 2 Width | 9.7 Cm |
Package 2 Length | 22.4 Cm |
Package 2 Weight | 1.464 Kg |
Unit Type of Package 3 | S03 |
Number of Units in Package 3 | 132 |
Package 3 Height | 30.0 Cm |
Package 3 Width | 30.0 Cm |
Package 3 Length | 40.0 Cm |
Package 3 Weight | 16.543 Kg |