Description
Main
Range of product Modicon X80
Product or component type Discrete output module
Discrete output number 64 conforming to EN/IEC 61131-2
Discrete output type Solid state
Discrete output logic Positive
Discrete output voltage 24 V 19…30 V DC
Discrete output current 0.1 A
Complementary
Current per channel 0.125 A
Maximum current per module 6.4 A
Insulation resistance > 10 MOhm 500 V DC
Power dissipation in W 6.85 W
Response time on output 1.2 ms
Paralleling of outputs Yes : 3 maximum
Typical current consumption 160 MA at 3.3 V DC
MTBF reliability 150000 H
Protection type External fuse reverse polarity protection
Short-circuit protection
Overload protection
overvoltage protection
Output overload protection With current limiter
With electronic circuit breaker 0.125 A < Id < 0.185 A
Output overvoltage protection With transil diode
Output short-circuit protection With 2 A external fuse
Reverse polarity protection Reverse mounted diode
Voltage detection threshold < 14 V DC preactuator fault
> 18 V DC preactuator at state 0
Maximum tungsten load 1.2 W
Switching frequency 0.5/LI2 Hz
Maximum overload time 15 Ms
Load impedance ohmic >= 220 Ohm
Status LED 1 LED (green) +32 channels indicator
1 LED (green) module operating (RUN)
1 LED per channel (green) channel diagnostic
1 LED (red) module error (ERR)
1 LED (red) module I/O
Net weight 0.15 Kg
Environment
IP degree of protection IP20
Directives 2014/35/EU – low voltage directive
2014/30/EU – electromagnetic compatibility
Dielectric strength 1500 V AC at 50/60 Hz 1 minute, output/ground
1500 V AC at 50/60 Hz 1 minute, output/internal logic
500 V DC 1 minute, between group of channels
Vibration resistance 3 gn
Shock resistance 30 gn
Ambient air temperature for storage -40…85 °C
Ambient air temperature for operation 0…60 °C
Relative humidity 5…95 % at 55 °C without condensation
Operating altitude 0…2000 m
2000…5000 m with derating factor