Main
Range of product Modicon X80
Product or component type Power supply module
Product compatibility Not compatible with BMEXBP..02
Primary voltage 100…240 V
Supply circuit type AC
Secondary power 15 W 3.3 V DC I/O module logic power supply
31.2 W 24 V DC I/O module power supply and processor
21.6 W 24 V DC sensor power supply
Complementary
Primary voltage limit 85…264 V
Network frequency 50/60 Hz
Network frequency limits 47…63 Hz
Apparent power 0.12 KVA
Input current 0.52 A 240 V
1.04 A 115 V
Inrush current 30 A 120 V
60 A 240 V
I2t on activation 1 A2.S 120 V
3 A2.S 240 V
It on activation 0.05 A.S 120 V
0.07 A.S 240 V
MTBF reliability 4300000 H
Protection type Internal fuse not accessible for primary circuit
Overload protection for secondary circuit
Overvoltage protection for secondary circuit
Short-circuit protection for secondary circuit
Current at secondary voltage 0.9 A 24 V DC sensor power supply
1.3 A 24 V DC I/O module power supply and processor
4.5 A 3.3 V DC I/O module logic power supply
Maximum power dissipation in W 8.5 W
Status LED 1 LED (green) rack voltage OK
1 LED (green) sensor voltage
Control type RESET push-button cold restart
Electrical connection 1 connector 2 pin(s)alarm relay
1 connector 5 pin(s)line supply, protective earth, 24 V DC input sensor
Insulation resistance >= 100 MOhm primary/ground
>= 100 MOhm primary/secondary
Net weight 0.36 Kg
Environment
Immunity to microbreaks 1 Ms
Dielectric strength 1500 V primary/secondary I/O module logic power supply
1500 V primary/secondary I/O module power supply and processor
2300 V primary/secondary sensor power supply
1500 V primary/ground
500 V 24 V sensor output/ground
Vibration resistance 3 gn
Shock resistance 30 gn
IP degree of protection IP20
Directives 2014/35/EU – low voltage directive
2014/30/EU – electromagnetic compatibility
Ambient air temperature for storage -40…85 °C
Ambient air temperature for operation 0…60 °C
Relative humidity 5…95 % at 55 °C without condensation
Protective treatment TC
Operating altitude 0…2000 m
2000…5000 m with derating factor