Phoenix Power Supply 10Amp Trio 240AC

R4,226.10

FloatOr as low as R845.22 / month interest-free, using your existing credit card. For orders over R100.00.How it works

TRIO-PS/1AC/24DC/10 – Power supply unit

 

Primary-switched TRIO POWER power supply for DIN rail mounting, input: 1-phase, output: 24 V DC/10 A

1 in stock

Categories: , SKU: PS10010

Description

Commercial data

Item number 2866310
Packing unit 1 pc
Minimum order quantity 1 pc
Sales key 090
Product key CMPT13
Catalog page Page 175 (C-6-2013)
GTIN 4046356046657
Weight per piece (incl. packing) 1 554 g
Weight per piece (excl. packing) 1 400 g
Customs tariff number 85044095
Country of origin CN

 

 

TRIO-PS/1AC/24DC/10 – Power supply unit

2866323 | My ID: PS10010

 

 

Technical data

Input data

AC operation

 

Parameter Specification
Nominal Input Voltage Range 100 V AC … 240 V AC
Input Voltage Range 85 V AC … 264 V AC (Derating < 90 V AC: 2.5 %/V)
Derating < 90 V AC: 2.5 %/V
Electric Strength Max. 300 V AC
Voltage Type of Supply Voltage AC
Inrush Current < 15 A
Inrush Current Integral (I2 t) 0.7 A2 s
AC Frequency Range 45 Hz … 65 Hz
Mains Buffering Time > 24 ms (120 V AC)

> 24 ms (230 V AC)

Current Consumption 3 A (100 V AC)

1.5 A (240 V AC)

Nominal Power Consumption 272 VA
Protective Circuit Transient surge protection; Varistor
Power Factor (cos phi) 0.99
Typical Response Time < 1 s
Input Fuse 6.3 A (slow-blow, internal)
Permissible Backup Fuse B6 B10 B16
Recommended Breaker for Input Protection 10 A … 16 A (Characteristics B, C, D, K)
Discharge Current to PE < 3.5 mA

 

Output data

Efficiency 89 % (for 230 V AC and nominal values)
Output characteristic U/I
Nominal output voltage 24 V DC ±1%
Setting range of output voltage (USet) 22.5 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IOUT) 10 A (UOUT = 24 V DC)
Derating 55 °C … 70 °C (2.5 %/K
Feedback voltage resistance 35 V DC
Protection against overvoltage (OVP) < 35 V DC
Max. capacitive load Unlimited
Active current limitation Approx. 14 A (for short-circuit)
Control deviation < 1% (change in load, static 10% … 90%)

< 2% (change in load, dynamic 10% … 90%)

< 0.1% (change in input voltage ±10%)

Residual ripple < 10 mVPP
Output power 240 W
Peak switching voltages nominal load < 50 mVPP

 

TRIO-PS/1AC/24DC/10 – Power supply unit

 

2866323 | My ID: PS10010

 

Maximum No-load Power Dissipation 6.7 W
Power Loss at Nominal Load (Max.) 30 W
Rise Time < 2 ms (UOUT 10% to 90%)
Connection in Parallel Yes, for redundancy and increased capacity
Connection in Series Yes

 

 

 

 

 

 

 

 

Connection data

 

Input

Connection method Screw connection
Conductor cross section, rigid min.  0.2 mm²
Conductor cross section, rigid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 9 mm
Screw thread M2.5
Tightening torque, min 0.4 Nm
Tightening torque, max 0.5 Nm

 

 

 

 

Output

Connection method Screw connection
Conductor cross section, rigid min. 0.2 mm²
Conductor cross section, rigid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section, AWG min 24
Conductor cross section AWG min. 14
Stripping length 9 mm
Screw thread M2.5
Tightening torque, min 0.4 Nm
Tightening torque, max 0.5 Nm

 

 

 

Signaling

Types of signaling LED
Operating voltage display Green LED

 

Signal output

Status display “DC OK” LED green
Note on status UOUT < 0.9 x UN : LED flashing

 

Electrical properties

Insulation voltage input/output 4 kV AC (type test)

2 kV AC (routine test)

Insulation voltage output / PE 500 V DC (type test)

 

TRIO-PS/1AC/24DC/10 – Power supply unit

 

Insulation voltage input / PE 2 kV AC (type test)

2 kV AC (routine test)

 

Product properties

 

Product type Power supply
Product family TRIO POWER
MTBF (IEC 61709, SN 29500) > 981000 h (40 °C)

 

Insulation characteristics

 

Protection class I (with PE connection)
Overvoltage category III
Degree of pollution 2

 

Dimensions

Dimensional drawing
Width 60 mm
Height 130 mm
Depth 152.5 mm

 

Installation dimensions

Installation distance right/left 0 mm / 0 mm
Installation distance top/bottom 50 mm / 50 mm

 

Mounting

Mounting type DIN rail mounting
Assembly note Alignable: horizontally 0 mm, vertically 50 mm
Mounting position Horizontal DIN rail NS 35, EN 60715
With protective coating No

 

Material specifications

 

Housing material Metal
Type of housing Steel sheet, zinc-plated
Side element version Aluminum

 

Environmental and real-life conditions

 

Ambient conditions

 

Degree of protection IP20
Ambient temperature (operation) -25 °C … 70 °C

(> 55° C derating : 2.5%/K)

Ambient temperature (storage/transport) -40 °C … 85 °C
Climatic class 3K3 (in acc. with EN 60721)
Max. permissible relative humidity ≤ 95 % (at 25 °C, non-condensing)

 

TRIO-PS/1AC/24DC/10 – Power supply unit

 

Shock 18 ms, 30g, in each space direction (according to IEC 60068-2- 27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)

15 Hz … 150 Hz, 2.3g, 90 min

 

 

 

Standards and regulations

 

Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard – Electrical safety  EN 60950-1/VDE 0805 (SELV)
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment EN 50178
Standard – Safety extra-low voltage EN 60950-1 (SELV)

EN 60204 (PELV)

Standard – Safe isolation DIN VDE 0100-410

 

 

Approvals

UL approvals  UL/C-UL listed UL 508

UL/C-UL Recognized UL 60950-1

 

 

Conformity/Approvals

 

SIL in accordance with IEC 61508 0

 

EMC data

Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
EMC Requirements for Noise Emission EN 61000-6-3

EN 61000-6-4

EMC Requirements for Noise Immunity EN 61000-6-1

EN 61000-6-2

Electromagnetic Compatibility Conformance with EMC Directive 2014/30/EU

 

Electrostatic discharge

Standards/Regulations EN 61000-4-2

 

Electrostatic discharge

Contact discharge 6 kV (Test Level 3
Discharge in air 8 kV (Test Level 3)
Comments Criterion A

 

Electromagnetic HF field

 

Standards/regulations EN 61000-4-3

 

 

Electromagnetic HF field

 

Frequency Range 80 MHz … 1 GHz
Test Field Strength 10 V/m
Frequency Range 1 GHz … 2 GHz
Test Field Strength 10 V/m

 

TRIO-PS/1AC/24DC/10 – Power supply unit

 

Frequency Range 2 GHz … 3 GHz
Test Field Strength 10 V/m
Comments Criterion A

 

Fast transients (burst)

 

Standards/regulations EN 61000-4-4

 

Fast transients (burst)

Input 4 kV (Test Level 4 – asymmetrical)
Output 4 kV (Test Level 4 – asymmetrical)
Signal  2 kV (Test Level 3 – asymmetrical)
Comments Criterion A

 

Surge voltage load (surge)

 

Standards/regulations EN 61000-4-5

 

Surge voltage load (surge)

 

Input 1 kV (Test Level 2 – symmetrical)

2 kV (Test Level 3 – asymmetrical)

Output 0.5 kV (Test Level 1 – symmetrical)

0.5 kV (Test Level 1 – asymmetrical)

Comments Criterion B

 

Conducted interference

 

Standards/regulations EN 61000-4-6

 

Conducted interference

 

Frequency Range 0.15 MHz … 80 MHz
Comments Criterion A
Voltage 10 V (Test Level 3)

 

Conducted interference

 

Frequency Range 0.15 MHz … 80 MHz
Comments Criterion A
Voltage 10 V (Test Level 3)

 

 

 

 

Voltage dips

 

Standards/regulations  EN 61000-4-11

 

Emitted interference

 

Standards/regulations  EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential

 

 

TRIO-PS/1AC/24DC/10 – Power supply unit

 

Classifications

 

ECLASS

ECLASS-11.0 27040701
ECLASS-12.0 27040701
ECLASS-13.0 27040701

 

ETIM

ETIM 8.0 EC002540

 

UNSPSC

UNSPSC 21.0 39121000

 

 

TRIO-PS/1AC/24DC/10 – Power supply unit

 

Environmental product compliance

 

EU RoHS

 

Fulfills EU RoHS substance requirements Yes
Exemption 7(a), 7(c)-I

 

China RoHS

Environment friendly use period (EFUP) EFUP-25

 

An article-related China RoHS declaration table can be found in the download area for the respective article under “Manufacturer declaration”. For all articles with EFUP-E, no China RoHS declaration table issued and required

 

EU REACH SVHC

 

REACH candidate substance (CAS No.) Lead(CAS: 7439-92-1)
SCIP 061338d1-7936-40eb-b79e-d37d0dc74e3b

 

 

TRIO-PS/1AC/24DC/10 – Power supply unit

 

Accessories

 

UWA 182/52 – Mounting adapter

 

Universal wall adapter for securely mounting the device in the event of strong vibrations. The device is screwed directly onto the mounting surface. The universal wall adapter is attached on the top/bottom.

UTA 107 – DIN rail adapter

 

Universal DIN rail adapter, for screwing on switchgear

 

TRIO-PS/1AC/24DC/10 – Power supply unit

 

PLT-SEC-T3-230-FM-UT – Type 3 surge protection device

 

Type 2/3 surge protection, consisting of protective plug and base element with screw connection. For single-phase power supply network with integrated status indicator and remote signaling. Nominal voltage: 230 V AC/DC

 

PLT-SEC-T3-24-FM-UT – Type 3 surge protection device

 

Type 3 surge protection, consisting of protective plug and base element, with integrated status indicator and remote signaling for single-phase power supply networks. Nominal voltage: 24 V AC/DC

Additional information

Weight 1.4 kg
Dimensions 15.2 × 6 × 13 cm