Description
Commercial data
Item number | 2866310 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | 090 |
Product key | CMPT13 |
Catalog page | Page 175 (C-6-2013) |
GTIN | 4046356046640 |
Weight per piece (incl. packing) | 749 g |
Weight per piece (excl. packing) | 618 g |
Customs tariff number | 85044095 |
Country of origin | CN |
TRIO-PS/1AC/24DC/ 5 – Power supply unit
2866310 | My ID: PS1005
Technical data
Input data
AC operation
Parameter | Specification |
Nominal Input Voltage Range | 100 V AC … 240 V AC |
Input Voltage Range | 85 V AC … 264 V AC (Derating < 90 V AC: 2.5 %/V) |
Derating | < 90 V AC: 2.5 %/V |
Electric Strength | Max. 300 V AC |
Voltage Type of Supply Voltage | AC |
Inrush Current | < 15 A |
Inrush Current Integral (I2 t) | 1.1 A2 s |
AC Frequency Range | 45 Hz … 65 Hz |
Mains Buffering Time | > 20 ms (120 V AC)
> 110 ms(230 V AC) |
Current Consumption | 1.65 A (120 V AC)
0.9 A (230 V AC) |
Nominal Power Consumption | 189 VA |
Protective Circuit | Transient surge protection; Varistor |
Power Factor (cos phi) | 0.72 |
Typical Response Time | < 1 s |
Input Fuse | 3.15 A (slow-blow, internal) |
Permissible Backup Fuse | B6 B10 B16 |
Recommended Breaker for Input Protection | 6 A … 16 A (Characteristics B, C, D, K) |
Discharge Current to PE | < 3.5 mA |
Output data
Efficiency | 89 % (for 230 V AC and nominal values) |
Output characteristic | U/I |
Nominal output voltage | 24 V DC ±1% |
Setting range of output voltage (USet) | 22.5 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted) |
Nominal output current (IOUT) | 5 A (UOUT = 24 V DC) |
Derating | 55 °C … 70 °C (2.5 %/K |
Feedback voltage resistance | 35 V DC |
Protection against overvoltage (OVP) | < 35 V DC |
Max. capacitive load | Unlimited |
Active current limitation | Approx. .10 A (for short-circuit) |
Control deviation | < 1% (change in load, static 10% … 90%)
< 2% (change in load, dynamic 10% … 90%) < 0.1% (change in input voltage ±10%) |
Residual ripple | < 20 mVPP |
Output power | 120 W |
Peak switching voltages nominal load | < 30 mVPP |
TRIO-PS/1AC/24DC/ 5 – Power supply unit
2866310 | My ID: PS1005
Maximum No-load Power Dissipation | 1.1 W |
Power Loss at Nominal Load (Max.) | 18 W |
Rise Time | < 2 ms (UOUT 10% to 90%) |
Connection in Parallel | Yes, for redundancy and increased capacity |
Connection in Series | Yes |
Connection data
Input
Connection method | Screw connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 14 |
Stripping length | 9 mm |
Screw thread | M2.5 |
Tightening torque, min | 0.4 Nm |
Tightening torque, max | 0.5 Nm |
Output
Connection method | Screw connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section, AWG min | 24 |
Conductor cross section AWG min. | 14 |
Stripping length | 9 mm |
Screw thread | M2.5 |
Tightening torque, min | 0.4 Nm |
Tightening torque, max | 0.5 Nm |
Signaling
Types of signaling | LED |
Operating voltage display | Green LED |
Signal output
Status display | “DC OK” LED green |
Note on status | display UOUT > 21.5 V: LED lights up |
Electrical properties
Insulation voltage input/output | 4 kV AC (type test)
2 kV AC (routine test) |
Insulation voltage output / PE | 500 V DC (type test) |
TRIO-PS/1AC/24DC/ 5 – Power supply unit
Insulation voltage input / PE | 2 kV AC (type test)
2 kV AC (routine test) |
Product properties
Product type | Power supply |
Product family | TRIO POWER |
MTBF (IEC 61709, SN 29500) | > 2054000 h |
Insulation characteristics
Protection class | I (with PE connection) |
Overvoltage category | III |
Degree of pollution | 2 |
Dimensions
Dimensional drawing | |
Width | 40 mm |
Height | 130 mm |
Depth | 115 mm |
Installation dimensions
Installation distance right/left | 0 mm / 0 mm |
Installation distance top/bottom | 50 mm / 50 mm |
Mounting
Mounting type | DIN rail mounting |
Assembly note | Alignable: horizontally 0 mm, vertically 50 mm |
Mounting position | Horizontal DIN rail NS 35, EN 60715 |
With protective coating | No |
Material specifications
Housing material | Metal |
Type of housing | Steel sheet, zinc-plated |
Side element version | Aluminum |
Environmental and real-life conditions
Ambient conditions
Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C … 70 °C
(> 55° C derating : 2.5%/K) |
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Climatic class | 3K3 (in acc. with EN 60721) |
Max. permissible relative humidity | ≤ 95 % (at 25 °C, non-condensing) |
TRIO-PS/1AC/24DC/ 5 – Power supply unit
Shock | 15g in all directions in acc. with IEC 60068-2-27 |
Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz … 150 Hz, 2.3g, 90 min |
Standards and regulations
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
Standard – Electrical safety | EN 60950-1/VDE 0805 (SELV) |
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment | EN 50178 |
Standard – Safety extra-low voltage | EN 60950-1 (SELV)
EN 60204 (PELV) |
Standard – Safe isolation | DIN VDE 0100-410 |
Approvals
Shipbuilding approval | DNV GL (EMC A) |
UL approvals | UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1 |
Conformity/Approvals
SIL in accordance with IEC 61508 | 0 |
EMC data
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
EMC Requirements for Noise Emission | EN 61000-6-3
EN 61000-6-4 |
EMC Requirements for Noise Immunity | EN 61000-6-1
EN 61000-6-2 |
Electromagnetic Compatibility | Conformance with EMC Directive 2014/30/EU |
Electrostatic discharge
Standards/Regulations | EN 61000-4-2 |
Electrostatic discharge
Contact discharge | 8 kV (Test Level 4) |
Discharge in air | 8 kV (Test Level 3) |
Comments | Criterion A |
Electromagnetic HF field
Standards/regulations | EN 61000-4-3 |
Electromagnetic HF field
Frequency Range | 80 MHz … 1 GHz |
Test Field Strength | 10 V/m |
Frequency Range | 1 GHz … 2 GHz |
Test Field Strength | 10 V/m |
TRIO-PS/1AC/24DC/ 5 – Power supply unit
Frequency Range | 2 GHz … 3 GHz |
Test Field Strength | 10 V/m |
Comments | Criterion A |
Fast transients (burst)
Standards/regulations | EN 61000-4-4 |
Fast transients (burst)
Input | 4 kV (Test Level 4 – asymmetrical) |
Output | 2 kV (Test Level 3 – asymmetrical) |
Comments | Criterion A |
Surge voltage load (surge)
Standards/regulations | EN 61000-4-5 |
Surge voltage load (surge)
Input | 1 kV (Test Level 2 – symmetrical)
2 kV (Test Level 3 – asymmetrical) |
Output | 0.5 kV (Test Level 1 – symmetrical)
0.5 kV (Test Level 1 – asymmetrical) |
Comments | Criterion B |
Conducted interference
Standards/regulations | EN 61000-4-6 |
Conducted interference
Frequency Range | 10 kHz to 15 kHz
10 kHz to 15 kHz |
Comments | Criterion A
Criterion A |
Voltage | 3 V (Test Level 2)
3 V (Test Level 2) |
Conducted interference
Frequency Range | 10 kHz to 15 kHz
10 kHz to 15 kHz |
Comments | Criterion A
Criterion A |
Voltage | 3 V (Test Level 2)
3 V (Test Level 2) |
Voltage dips
Standards/regulations | EN 61000-4-11 |
Emitted interference
Standards/regulations | EN 61000-6-3 |
TRIO-PS/1AC/24DC/ 5 – Power supply unit
Emitted radio interference in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Emitted radio interference in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |