General technical data
size of contactor 3
product extension auxiliary switch Yes
power loss [W] for rated value of the current at AC in hot operating state 22.176 W
● per pole 7.392 W
insulation voltage
● of main circuit with degree of pollution 3 rated value 1 000 V
● of auxiliary circuit with degree of pollution 3 rated value 1 000 V
surge voltage resistance
● of main circuit rated value 8 kV
● of auxiliary circuit rated value 6 kV
protection class IP
● on the front IP20
mechanical service life (operating cycles)
● of contactor typical 5 000 000
reference code according to IEC 81346-2 Q
Substance Prohibitance (Date) 07/01/2022
Weight 1.082 kg

Main circuit
number of poles for main current circuit 3
number of NO contacts for main contacts 3
operating voltage at AC-3 rated value maximum 690 V
operational current
● at AC-1 at 400 V at ambient temperature 40 °C rated value 80 A
● at AC-1 up to 690 V
— at ambient temperature 40 °C rated value 80 A
— at ambient temperature 60 °C rated value 65 A
● at AC-3
— at 400 V rated value 50 A
— at 690 V rated value 24 A
operating power
● at AC-3
— at 400 V rated value 22 kW
— at 690 V rated value 22 kW
no-load switching frequency
● at AC 1 200 1/h
operating frequency
● at AC-1 maximum 600 1/h
● at AC-3 maximum 600 1/h

Auxiliary circuit
number of NC contacts for auxiliary contacts
● instantaneous contact 1
number of NO contacts for auxiliary contacts
● instantaneous contact 1
operational current at AC-12 maximum 10 A
operational current at AC-15
● at 230 V rated value 6 A
● at 400 V rated value 3 A
● at 500 V rated value 2 A
● at 690 V rated value 1 A
operational current at DC-12
● at 24 V rated value 6 A
● at 110 V rated value 3 A
● at 220 V rated value 1 A
operational current at DC-13
● at 24 V rated value 6 A
● at 110 V rated value 1 A
● at 220 V rated value 0.3 A