SIEMENS MCCB FS1 3P 125A 36KA

R2,051.17

circuit breaker 3VJ1 IEC MCCB_FS1_125A Line protection ATFM 3 Pole Ics=Icu=36kA@415V In=80A overload protection Ir=64A..80A short-circuit protection Ii=10 x In Screw connection

Pay in 3 or 12. The Clever Way to Pay.
From over 12 months or 3 interest free payments.
Learn more...

Your flexible payment provider.

Example payment for

x 3
0% interest, zero fees.
Pay in 3
x 12
28.25% interest, plus fees.
Total Payment
Pay in 12

How does PayJustNow work?

  • Shop and choose PayJustNow at checkout.
  • Sign up and get instant approval.
  • Pay in 3 or 12.

You can complete sign-up in under 2 minutes - no need to leave your cart!

3 in stock

Or as low as R410.24 over 5 months interest free, using your credit card. For orders over R1.00.How it works
Categories: , SKU: 3VJ1108-6DB32-0AA0 Brand:

Description

Model
product designation Molded Case Circuit Breaker
design of the product Line protection
design of the overcurrent release ATFM
protection function of the overcurrent release LI
number of poles 3

General technical data
insulation voltage / rated value 1 000 V
operating voltage / at AC / rated value 415 V
power loss [W] / maximum 31.5 W
power loss [W] / for rated value of the current / at AC / in hot operating
state / per pole

10.5 W
mechanical service life (operating cycles) / typical 15 000
electrical endurance (operating cycles) / at AC-1 / at 380/415 V 5 000
ground-fault monitoring version without
Net Weight 1.42 kg

Current
operational current
● at 40 °C 80 A
● at 45 °C 80 A
● at 50 °C 80 A
● at 55 °C 77.76 A
● at 60 °C 75.52 A

Switching capacity according to IEC 60947
maximum short-circuit current breaking capacity (Icu)
● at 415 V 36 kA
operating short-circuit current breaking capacity (Ics)
● at 415 V 36 kA
short-circuit current making capacity (Icm)
● at 415 V 121 kA

Adjustable parameters
adjustable current response value current / of the current-dependent
overload release

64 … 80 A
adjustable current response value current / of instantaneous short-circuit
trip unit
● minimum 800 A
● maximum 800 A
product function / grounding protection No

Mechanical Design
height 150 mm
width 92 mm
depth 85 mm
Connections
arrangement of electrical connectors / for main current circuit Front connection
type of electrical connection / for main current circuit Lug connection line and load side

Accessories
product extension / optional / motor drive No

Environmental conditions
protection class IP / on the front IP42
ambient temperature

● during operation / minimum -10 °C
● during operation / maximum 60 °C
● during storage / minimum -15 °C
● during storage / maximum 75 °C