SIEMENS MCCB S00 A 2.8-4A N 52A

R1,565.36

Circuit breaker size S00 for motor protection, CLASS 10 A-release 2.8…4 A N release 52 A screw terminal Standard switching capacity

Pay in 3 or 12. The Clever Way to Pay.
From over 12 months or 3 interest free payments.
Learn more...

Your flexible payment provider.

Example payment for

x 3
0% interest, zero fees.
Pay in 3
x 12
28.25% interest, plus fees.
Total Payment
Pay in 12

How does PayJustNow work?

  • Shop and choose PayJustNow at checkout.
  • Sign up and get instant approval.
  • Pay in 3 or 12.

You can complete sign-up in under 2 minutes - no need to leave your cart!

5 in stock

Or as low as R313.08 over 5 months interest free, using your credit card. For orders over R1.00.How it works
Categories: , SKU: 3RV2011-1EA10 Brand:

Description

General technical data
size of the circuit-breaker S00
size of contactor can be combined company-specific S00, S0
product extension auxiliary switch Yes
power loss [W] for rated value of the current
● at AC in hot operating state 7.25 W
● at AC in hot operating state per pole 2.4 W
insulation voltage with degree of pollution 3 at AC rated value 690 V
surge voltage resistance rated value 6 kV
shock resistance according to IEC 60068-2-27 25g / 11 ms
mechanical service life (operating cycles)
● of the main contacts typical 100 000
● of auxiliary contacts typical 100 000
electrical endurance (operating cycles) typical 100 000
reference code according to IEC 81346-2 Q
Substance Prohibitance (Date) 10/01/2009
SVHC substance name Lead – 7439-92-1
Weight 0.346 kg

Main circuit
number of poles for main current circuit 3
adjustable current response value current of the current-dependent
overload release

2.8 … 4 A
type of voltage for main current circuit AC/DC
operating voltage
● rated value 20 … 690 V
● at AC-3 rated value maximum 690 V
● at AC-3e rated value maximum 690 V
operating frequency rated value 50 … 60 Hz
operational current rated value 4 A
operational current

● at AC-3 at 400 V rated value 4 A
● at AC-3e at 400 V rated value 4 A
operating power
● at AC-3
— at 230 V rated value 0.8 kW
— at 400 V rated value 1.5 kW
— at 500 V rated value 2.2 kW
— at 690 V rated value 3 kW
● at AC-3e
— at 230 V rated value 0.8 kW
— at 400 V rated value 1.5 kW
— at 500 V rated value 2.2 kW
— at 690 V rated value 3 kW
operating frequency
● at AC-3 maximum 15 1/h
● at AC-3e maximum 15 1/h

Auxiliary circuit
type of voltage for auxiliary and control circuit AC/DC
number of NC contacts for auxiliary contacts 0
number of NO contacts for auxiliary contacts 0
number of CO contacts for auxiliary contacts 0

Installation/ mounting/ dimensions
mounting position any
fastening method screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
height 97 mm
width 45 mm
depth 97 mm
required spacing
● with side-by-side mounting at the side 0 mm
● for grounded parts at 400 V
— downwards 30 mm
— upwards 30 mm

— at the side 9 mm
● for live parts at 400 V
— downwards 30 mm
— upwards 30 mm
— at the side 9 mm
● for grounded parts at 500 V
— downwards 30 mm
— upwards 30 mm
— at the side 9 mm
● for live parts at 500 V
— downwards 30 mm
— upwards 30 mm
— at the side 9 mm
● for grounded parts at 690 V
— downwards 50 mm
— upwards 50 mm
— backwards 0 mm
— at the side 30 mm
— forwards 0 mm
● for live parts at 690 V
— downwards 50 mm
— upwards 50 mm
— backwards 0 mm
— at the side 30 mm
— forwards 0 mm