Description
Main
Range TeSys
TeSys Deca
Product or component type Undervoltage release
Device short name GVAU
Complementary
Range compatibility TeSys GV2ME[RETURN]TeSys GV2LE[RETURN]TeSys GV2L[RETURN]TeSys-
GV2P[RETURN]TeSys GV3L[RETURN]TeSys GV3P[RETURN]TeSys Deca
[Uc] control circuit voltage 380…400 V AC 50 Hz
440 V AC 60 Hz
Control circuit voltage limits 0.85…1.1 Un
[Ui] rated insulation voltage 690 V AC conforming to IEC 60947-1
600 V AC conforming to UL 60947-4-1
600 V AC conforming to CSA C22.2 No 60947-4-1
Threshold tripping voltage 0.7…0.35 Un
Inrush power in VA 12 VA AC
Inrush power in W 8 W
Hold-in power consumption in VA 3.5 VA AC
Hold-in power consumption in W 1.1 W
Operating time 10…15 ms conforming to IEC 60947-1
On-load factor 100 %
Connections – terminals Screw clamp terminals 1 cable(s) 1…2.5 mm2solid
Screw clamp terminals 2 cable(s) 1…2.5 mm2solid
Screw clamp terminals 1 cable(s) 0.75…2.5 mm2flexible without cable end
Screw clamp terminals 2 cable(s) 0.75…2.5 mm2flexible without cable end
Screw clamp terminals 1 cable(s) 0.75…1.5 mm2flexible with cable end
Screw clamp terminals 2 cable(s) 0.75…1.5 mm2flexible with cable end
Tightening torque < 1.4 N.m on screw clamp terminals
Mechanical durability 10000 Cycles with GV3P and GV3L
30000 Cycles with GV2ME and GV2P
Quantity per set Set of 10
Height 89 Mm
Width 18 Mm
Depth 66 Mm
Net weight 0.105 Kg
Colour Dark grey