Description
Main
Range TeSys
Range of product TeSys U
TeSys GV2
Accessory / separate part category Protection accessory
Product or component type Current limiting module
Range compatibility TeSys TeSys U
TeSys TeSys GV2
Product compatibility LUB
LU2B
GV2P
GV2L
GV2RT
GV2ME
Function of module Increasing the breaking capacity of a circuit breaker
Mounting location 35 mm DIN rail
[Ie] rated operational current 32 A
[Ith] conventional free air thermal current 63 A conforming to IEC 60947-1
Activation threshold 1000 A
Breaking capacity <= 100 kA depending on protective device
[Ue] rated operational voltage 690 V AC 50/60 Hz
[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-1
Complementary
Connections – terminals Screw clamp terminals 1 x 1.5…25 mm2 rigid
Screw clamp terminals 2 x 1.5…10 mm2 rigid
Screw clamp terminals 1 x 1.5…25 mm2 flexible without cable end
Screw clamp terminals 2 x 1.5…10 mm2 flexible without cable end
Screw clamp terminals 1 x 1.5…16 mm2 flexible with cable end
Screw clamp terminals 2 x 1.5…4 mm2 flexible with cable end
Tightening torque 2.2 N.M
Net weight 0.32 Kg