ACTI9 MCB C120N 1P 125A 10KA C

R740.01

Miniature circuit-breaker. Acti9
C120N. 1 pole. 125 A. C curve.
10000 A (IEC 60898-1). 10 kA (IEC
60947-2)

Pay over 3 EQUAL zero-interest instalments of R246.67 with PayJustNow.
Find out how...

HOW IT WORKS

PayJustNow allows you to pay for your purchase over 3 payments with 0% interest and no fees. Pay a third at checkout and receive your goods immediately. The remaining two instalments are debited on your selected instalment dates.

Browse online or in-store and proceed to checkout

Choose PayJustNow as your payment method

Create your account and receive an instant approval decision

Complete your transaction

WHAT YOU WILL NEED

Be over 18 years old

Be a South African resident

Have a debit or credit card

Have a valid email address

0% INTEREST. 3 PAYMENTS. NO STRESS.

WHY PAY ANY OTHER WAY?

6 in stock

Or as low as R148.01 over 5 months interest free, using your credit card. For orders over R0.01.How it works
Categories: , SKU: A9N18359 Brand:

Description

Main
Range Acti9
product name Acti9 C120
Product or component type Miniature circuit-breaker
Device short name C120N
Device application Distribution
Poles description 1P
Number of protected poles 1
[In] rated current 125 A at 30 °C
network type AC
Trip unit technology Thermal-magnetic
Curve code C
Breaking capacity 3 kA Icu at 380…415 V AC 50/60 Hz IT conforming to EN/IEC 60947-2
20 kA Icu at 130 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 12 V DC conforming to EN/IEC 60947-2
15 kA Icu at 125 V DC conforming to EN/IEC 60947-2
10 kA Icu at <= 144 V DC conforming to EN/IEC 60947-2
10 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 12 V AC 50/60 Hz conforming to EN/IEC 60947-2
10000 A Icn at 230…400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Suitability for isolation Yes conforming to IEC 60947-2
Standards EN/IEC 60898-1
EN/IEC 60947-2
Product certifications EAC

Complementary
Network frequency 50/60 Hz
[Ue] rated operational voltage 380…415 V AC 50/60 Hz
125 V DC
<= 144 V DC
12 V DC
220…240 V AC 50/60 Hz
230…400 V AC 50/60 Hz
130 V AC 50/60 Hz
12 V AC 50/60 Hz
Magnetic tripping limit 5…10 x In

[Ics] rated service breaking
capacity
15 kA 75 % conforming to EN/IEC 60947-2 – 130 V AC 50/60 Hz
15 kA 100 % conforming to EN/IEC 60947-2 – 125 V DC
2.25 kA 75 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
15 kA 100 % conforming to EN/IEC 60947-2 – 12 V DC
10 kA 100 % conforming to EN/IEC 60947-2 – <= 144 V DC
7.5 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 – 12 V AC 50/60 Hz
7500 A 75 % conforming to EN/IEC 60898-1 – 230…400 V AC 50/60 Hz
Limitation class 3 conforming to EN/IEC 60947-2
[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand
voltage
6 kV conforming to EN/IEC 60947-2
Contact position indicator Yes
control type Toggle
Local signalling ON/OFF indication
Mounting mode Clip-on
Mounting support 35 mm symmetrical DIN rail
Comb busbar and distribution
block compatibility
YES
9 mm pitches 3
Height 81 mm
Depth 73 mm
Width 27 mm
Net weight 0.205 kg
Colour White
Mechanical durability 20000 cycles
Electrical durability 5000 cycles conforming to IEC 60947-2
Locking options description Handle sealable with cable diameter 0.7mm in OFF or

Connections – terminals Tunnel type terminals1…50 mm² rigid
Tunnel type terminals1.5…35 mm² flexible
Wire stripping length 15 mm
Tightening torque 3.5 N.m
Earth-leakage protection Without

Environment
IP degree of protection IP20 conforming to IEC 60529
Pollution degree 3 conforming to IEC 60947-2
overvoltage category IV
Tropicalisation 2 conforming to IEC 60068-1
Relative humidity 95 % at 55 °C
Operating altitude 2000 m
Ambient air temperature for
operation
-25…70 °C
Ambient air temperature for
storage
-40…85 °C