Description
Main
Range Acti9
Product name Acti9 Vigi iC60
Product or component type Add-on residual current device
Device short name Vigi iC60
Poles description 2P
[In] rated current 25 A
Earth-leakage sensitivity 100 MA
Earth-leakage protection time delay Instantaneous
Earth-leakage protection class Type AC
Network type AC
Network frequency 50/60 Hz
[Ue] rated operational voltage 230…415 V AC 50/60 Hz conforming to EN/IEC 61009-1
230…415 V AC 50/60 Hz conforming to EN/IEC 61009-2-1
Standards EN/IEC 61009-1
EN/IEC 61009-2-1
9 mm pitches 3
Complementary
Device location in system Outgoer
Residual current tripping technology Voltage independent
[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 6 KV conforming to IEC 60947-2
Range compatibility Acti 9 Acti9 iC60
Acti 9 Acti9 Reflex iC60
Product compatibility Single terminal
Local signalling Trip indicator
Mounting mode Clip-on
Mounting support DIN rail
Electrical connection to mcb By screws
Comb busbar and distribution block compatibility Bottom: YES
Height 91 Mm
Width 63 Mm
Depth 73.5 Mm
Net weight 0.165 Kg
Connections – terminals Tunnel type terminal downside for 1 cable(s) 1…25 mm2 rigid without cable end
Tunnel type terminal downside for 1 cable(s) 1…16 mm2 flexible without ca-
ble end
Tunnel type terminal downside for 1 cable(s) 1…16 mm2 flexible with cable end
Wire stripping length 14 Mm for bottom connection
Tightening torque 2 N.M bottom
Environment
IP degree of protection IP20 conforming to IEC 60529
IP40 (modular enclosure) conforming to IEC 60529
Pollution degree 3 conforming to IEC 60947-2
Electromagnetic compatibility 8/20 μs impulse withstand, 250 A conforming to IEC 61009-1
Ambient air temperature for operation -5…60 °C
Ambient air temperature for storage -40…85 °C
