Description
Main
Range Acti9
Product name Acti9 Vigi iC60
Product or component type Add-on residual current device
Device short name Vigi iC60
Poles description 4P
[In] rated current 63 A
Earth-leakage sensitivity 100 MA
Earth-leakage protection time delay Instantaneous
Earth-leakage protection class Type AC
Network type AC
Network frequency 50/60 Hz
[Ue] rated operational voltage 230…415 V AC 50/60 Hz conforming to EN/IEC 61009-1
230…415 V AC 50/60 Hz conforming to EN/IEC 61009-2-1
Standards EN/IEC 61009-1
EN/IEC 61009-2-1
9 mm pitches 7
Complementary
Device location in system Outgoer
Residual current tripping technology Voltage independent
[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 6 KV conforming to IEC 60947-2
Range compatibility Acti 9 Acti9 iC60
Acti 9 Acti9 Reflex iC60
Product compatibility Single terminal
Local signalling Trip indicator
Mounting mode Clip-on
Mounting support DIN rail
Electrical connection to mcb By screws
Comb busbar and distribution block compatibility Bottom: YES
Height 91 Mm
Width 135 Mm
Depth 73.5 Mm
Net weight 0.245 Kg
Connections – terminals Tunnel type terminal downside for 1 cable(s) 1…35 mm2 rigid without cable end
Tunnel type terminal downside for 1 cable(s) 1…25 mm2 flexible without ca-
ble end
Tunnel type terminal downside for 1 cable(s) 1…25 mm2 flexible with cable end
Wire stripping length 14 Mm for bottom connection
Tightening torque 3.5 N.M bottom
Environment
IP degree of protection IP20 conforming to IEC 60529
IP40 (modular enclosure) conforming to IEC 60529
Pollution degree 3 conforming to IEC 60947-2
Electromagnetic compatibility 8/20 μs impulse withstand, 250 A conforming to IEC 61009-1
Ambient air temperature for operation -5…60 °C
Ambient air temperature for storage -40…85 °C