Range of product Harmony Electromechanical Relays
Series name RSL series
Product or component type Plug-in relay
Relay type Slim interface relay
Contact operation Standard
Contacts type and composition 1 C/O
Control type Without lockable test button
Status LED Without
[Uc] control circuit voltage 24 V DC
[Ithe] conventional enclosed thermal current 6 A at -40…55 °C
Complementary
[Uimp] rated impulse withstand voltage 6 KV conforming to IEC
[Ie] rated operational current 6 A (AC-1/DC-1) conforming to IEC/UL
Minimum switching current 100 MA
Minimum switching voltage 12 V
Minimum switching capacity 120 mW
Rated operational voltage limits 18…33.6 V DC
[Ui] rated insulation voltage 250 V conforming to IEC
277 V conforming to cUL
Operating time 5 ms reset
12 ms
Maximum switching voltage 277 V
Drop-out voltage threshold >= 0.05 Uc
Load current 6 A at 250 V AC 0.5 mm mounting distance
Maximum switching capacity 1500 VA
150 W
Terminals description ISO n°1 (11-12-14)OC
(A1-A2)CO
Average resistance 3390 Ohm at 23 °C +/- 15 %
Average coil consumption 0.17 W
Mechanical durability 10000000 Cycles
Electrical durability 60000 Cycles, 6 A at 250 V, AC-1 C/O
Safety reliability data B10d = 60000
Operating rate <= 360 cycles/hour under load
<= 18000 cycles/hour no-load
Protection category RT III
Mounting support Socket or PCB
Operating position Any position
Test levels Level A group mounting
Device presentation Complete product
Contacts material Silver alloy (AgSnO2)
Shape of pin Flat (PCB type)
Width 5 Mm
Height 28 Mm
Depth 18.5 Mm
Net weight 0.0054 Kg
Environment
Dielectric strength 1000 V AC between contacts
4000 V AC between coil and contact
Vibration resistance +/- 1 mm (f= 10…55 Hz) conforming to IEC 60068-2-6
IP degree of protection IP40 conforming to IEC 60529
Ambient air temperature for operation -40…55 °C
Standards CSA C22.2 No 14
IEC 61810-1
UL 508
Product certifications CSA[RETURN]UL[RETURN]EAC
Ambient air temperature for storage -40…70 °C
Shock resistance 5 gn (duration = 11 ms) for not operating conforming to IEC 60068-2-27
5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27