Thermal overload relay, TeSys Deca, 690VAC, 1 to 1.6A, 1NO+1NC, class 10A, screw clamp

Open Fact Sheet

5 in stock

Categories: , SKU: LRD06

Description

 

Main

Range TeSys

TeSys Deca

Product name TeSys LRD

TeSys Deca

Product or component type Differential thermal overload relay
Device short name LRD
Relay application Motor protection
Product compatibility LC1D25

LC1D32

LC1D12

LC1D18

LC1D38

LC1D09

Network type DC

AC

Thermal overload class Class 10A conforming to IEC 60947-4-1
Thermal protection adjustment range 1 …1.6 A
[Ui] rated insulation voltage Power circuit: 600 V conforming to CSA

Power circuit: 600 V conforming to UL

Power circuit: 690 V conforming to IEC 60947-4-1

 

 

Complementary

Network frequency 0…400 Hz
Mounting support Plate, with specific accessories

Rail, with specific accessories

Under contactor

Tripping threshold 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
Auxiliary contact composition 1 NO + 1 NC
[Ith] conventional free air thermal current 5 A for signalling circuit
Permissible current 3 A at 120 V AC-15 for signalling circuit

0.22 A at 125 V DC-13 for signalling circuit

[Ue] rated operational voltage 690 V AC 0…400 Hz for power circuit conforming to IEC 60947-4-1
Associated fuse rating 4 A gG for signalling circuit

4 A BS for signalling circuit

[Uimp] rated impulse withstand voltage 6 KV
Phase failure sensitivity Tripping current 130 % of Ir on two phase, the last one at 0
Control type Red push-button: stop

Blue push-button: reset

Temperature compensation -20…60 °C
Connections – terminals Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible without cable end

Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible with cable end

Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² solid without cable end

Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm² flexible without cable end

Power circuit: screw clamp terminals 1 cable(s) 1…4 mm² flexible with cable end

Power circuit: screw clamp terminals 1 cable(s) 1…6 mm² solid without cable end

Tightening torque Control circuit: 1.7 N.m – on screw clamp terminals

Power circuit: 1.7 N.m – on screw clamp terminals

Height 66 Mm
Width 45 Mm
Depth 70 Mm
Net weight 0.124 Kg

 

Environment

 

Climatic withstand Conforming to IACS E10
IP degree of protection IP20 conforming to IEC 60529
Ambient air temperature for operation -20…60 °C without derating conforming to IEC 60947-4-1
Ambient air temperature for storage -60…70 °C
Flame retardance V1 conforming to UL 94
Mechanical robustness Vibrations: 6 Gn conforming to IEC 60068-2-6

Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7

Dielectric strength 1.89 KV at 50 Hz conforming to IEC 60947-1
Standards EN/IEC 60947-4-1

EN/IEC 60947-5-1

UL 60947-4-1

UL 60947-5-1

CSA C22.2 No 60947-4-1

CSA C22.2 No 60947-5-1

GB/T 14048.4

GB/T 14048.5

EN 50495

Product certifications IEC[RETURN]UL[RETURN]CSA[RETURN]CCC[RETURN]EAC[RETURN]BV[RETURN]

RINA[RETURN]DNV-GL[RETURN]LROS (Lloyds register of shipping)[RETURN]

ATEX INERIS[RETURN]UKCA

 

Packing Units

 

Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 4.900 Cm
Package 1 Width 7.700 Cm
Package 1 Length 8.800 Cm
Package 1 Weight 141.900 G
Unit Type of Package 2 S02
Number of Units in Package 2 24
Package 2 Height 15.000 Cm
Package 2 Width 30.000 Cm
Package 2 Length 40.000 Cm
Package 2 Weight 3.649 Kg

 