Phoenix Power Supply 20Amp Trio 240AC

R5,352.33

TRIO-PS/1AC/24DC/20 – Power supply unit

 

Primary-switched TRIO POWER power supply for DIN rail mounting, input: 1-phase, output: 24 V DC/20 A

Pay over 3 EQUAL zero-interest instalments of R1,784.11 with PayJustNow.
Find out how...

HOW IT WORKS

PayJustNow allows you to pay for your purchase over 3 payments with 0% interest and no fees. Pay a third at checkout and receive your goods immediately. The remaining two instalments are debited on your selected instalment dates.

Browse online or in-store and proceed to checkout

Choose PayJustNow as your payment method

Create your account and receive an instant approval decision

Complete your transaction

WHAT YOU WILL NEED

Be over 18 years old

Be a South African resident

Have a debit or credit card

Have a valid email address

0% INTEREST. 3 PAYMENTS. NO STRESS.

WHY PAY ANY OTHER WAY?

2 in stock

Or as low as R1,070.47 over 5 months interest free, using your credit card. For orders over R0.01.How it works
Categories: , SKU: PS10020 Brand:

Description

Commercial data

Item number2866310
Packing unit1 pc
Minimum order quantity1 pc
Sales key090
Product keyCMPT13
Catalog pagePage 175 (C-6-2013)
GTIN4046356046657
Weight per piece (incl. packing)2 354 g
Weight per piece (excl. packing)2 084 g
Customs tariff number85044095
Country of originCN

 

TRIO-PS/1AC/24DC/20 – Power supply unit

2866381

 

Technical data

 Input data

AC operation

 

ParameterSpecification
Nominal Input Voltage Range100 V AC … 240 V AC
Input Voltage Range85 V AC … 264 V AC (Derating < 90 V AC: 2.5 %/V)
Derating< 90 V AC: 2.5 %/V
Input voltage range AC85 V AC … 264 V AC (Derating < 90 V AC: 2,5 %/V)
Electric StrengthMax. 300 V AC
Voltage Type of Supply VoltageAC
Inrush Current< 15 A
Inrush Current Integral (I2 t)1.4 A2 s
AC Frequency Range45 Hz … 65 Hz
Mains Buffering Time> 13 ms (120 V AC)

> 13 ms (230 V AC)

Current Consumption4.6 A (120 V AC)

2.4 A (230 V AC)

Nominal Power Consumption533 VA
Protective CircuitTransient surge protection; Varistor
Power Factor (cos phi)0.99
Typical Response Time< 1 s
Input Fuse10 A (slow-blow, internal)
Permissible Backup FuseB16
Recommended Breaker for Input Protection16 A (Characteristics B, C, D, K)
Discharge Current to PE< 3.5 mA

 

Output data

Efficiency91 % (for 230 V AC and nominal values)
Output characteristicU/I
Nominal output voltage24 V DC ±1%
Setting range of output voltage (USet)22.5 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IOUT)20 A (UOUT = 24 V DC)
Derating55 °C … 70 °C (2.5 %/K
Feedback voltage resistance35 V DC
Protection against overvoltage (OVP)< 35 V DC
Max. capacitive loadUnlimited
Active current limitationApprox. 25 A (for short-circuit)
Control deviation< 1% (change in load, static 10% … 90%)

< 2% (change in load, dynamic 10% … 90%)

< 0.1% (change in input voltage ±10%)

Residual ripple< 10 mVPP
Output power480 W
Peak switching voltages nominal load< 80 mVPP

 

TRIO-PS/1AC/24DC/20 – Power supply unit

 

2866381

 

Maximum No-load Power Dissipation4 W
Power Loss at Nominal Load (Max.)46 W
Rise Time< 2 ms (UOUT 10% to 90%)
Connection in ParallelYes, for redundancy and increased capacity
Connection in SeriesYes

 

 

 

 

 

 

 

 

Connection data

 

Input

Connection methodScrew connection
Conductor cross section, rigid min. 0.2 mm²
Conductor cross section, rigid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.14
Stripping length9 mm
Screw threadM2.5
Tightening torque, min0.4 Nm
Tightening torque, max0.5 Nm

 

 

 

 

Output

Connection methodScrew connection
Conductor cross section, rigid min.0.5 mm²
Conductor cross section, rigid max.6 mm²
Conductor cross section flexible min.0.5 mm
Conductor cross section flexible max.4 mm²
Conductor cross section, AWG min20
Conductor cross section AWG max.10
Stripping length14 mm
Screw threadM3
Tightening torque, min0.5 Nm
Tightening torque, max0.6 Nm

 

 

 

 

Signaling

Types of signalingLED
Operating voltage displayGreen LED

 

Signal output

Status display“DC OK” LED green
Note on statusUOUT < 0.9 x UN : LED flashing

 

Electrical properties

Insulation voltage input/output4 kV AC (type test)

2 kV AC (routine test)

Insulation voltage output / PE500 V DC (type test)

 

TRIO-PS/1AC/24DC/20 – Power supply unit

 

Insulation voltage input/output2 kV (routine test)
Insulation voltage input / PE2 kV AC (type test)

2 kV AC (routine test)

Insulation voltage input, output / housing 4 kV (type test)

 

Product properties

 

Product typePower supply
Product familyTRIO POWER
MTBF (IEC 61709, SN 29500)> 915000 h

 

Insulation characteristics

 

Protection classI (with PE connection)
Overvoltage categoryIII
Degree of pollution2

 

Dimensions

Dimensional drawing
Width115 mm
Height130 mm
Depth152.5 mm

 

 

 

Installation dimensions

Installation distance right/left0 mm / 0 mm
Installation distance top/bottom50 mm / 50 mm

 

Mounting

Mounting typeDIN rail mounting
Assembly noteAlignable: horizontally 0 mm, vertically 50 mm
Mounting positionHorizontal DIN rail NS 35, EN 60715
With protective coatingNo

 

Material specifications

 

Housing materialMetal
Type of housingSteel sheet, zinc-plated
Side element versionAluminum

 

Environmental and real-life conditions

 

Ambient conditions

 

Degree of protectionIP20
Ambient temperature (operation)-25 °C … 70 °C

(> 55° C derating : 2.5%/K)

Ambient temperature (storage/transport)-40 °C … 85 °C

 

 

 

 

 

 

TRIO-PS/1AC/24DC/20 – Power supply unit

 

Climatic class3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)≤ 95 % (at 25 °C, non-condensing)
Shock18 ms, 30g, in each space direction (according to IEC 60068-2- 27)
Vibration (operation)< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)

15 Hz … 150 Hz, 2.3g, 90 min

 

Standards and regulations

Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installationsEN 50178/VDE 0160 (PELV)
Standard – Limitation of mains harmonic currentsEN 61000-3-2
Standard – Electrical safety EN 60950-1/VDE 0805 (SELV)
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipmentEN 50178
Standard – Safety extra-low voltageEN 60950-1 (SELV)

EN 60204 (PELV)

Standard – Safe isolationDIN VDE 0100-410

 

Approvals

UL approvals UL/C-UL listed UL 508

UL/C-UL Recognized UL 60950-1

 

Conformity/Approvals

 

SIL in accordance with IEC 615080

 

 

 

 

 

 

EMC data

Low Voltage DirectiveConformance with Low Voltage Directive 2014/35/EC
EMC Requirements for Noise EmissionEN 61000-6-3

EN 61000-6-4

EMC Requirements for Noise ImmunityEN 61000-6-1

EN 61000-6-2

Electromagnetic CompatibilityConformance with EMC Directive 2014/30/EU

 

Electrostatic discharge

Standards/RegulationsEN 61000-4-2

 

Electrostatic discharge

Contact discharge8 kV (Test Level 4)
Discharge in air8 kV (Test Level 3)
CommentsCriterion A

 

Electromagnetic HF field

Standards/regulationsEN 61000-4-3

 

Electromagnetic HF field

 

Frequency Range80 MHz … 1 GHz
Test Field Strength10 V/m

 

TRIO-PS/1AC/24DC/20 – Power supply unit

 

Frequency Range1 GHz … 2 GHz
Test Field Strength10 V/m
Frequency range 2 GHz … 3 GHz
Test field strength10 V/m
CommentsCriterion A

 

Fast transients (burst)

 

Standards/regulationsEN 61000-4-4

 

Fast transients (burst)

Input4 kV (Test Level 4 – asymmetrical)
Output4 kV (Test Level 4 – asymmetrical)
Signal 2 kV (Test Level 3 – asymmetrical)
CommentsCriterion A

 

Surge voltage load (surge)

 

Standards/regulationsEN 61000-4-5

 

Surge voltage load (surge)

 

Input1 kV (Test Level 2 – symmetrical)

2 kV (Test Level 3 – asymmetrical)

Output0.5 kV (Test Level 1 – symmetrical)

0.5 kV (Test Level 1 – asymmetrical)

CommentsCriterion B

 

Conducted interference

 

Standards/regulationsEN 61000-4-6

 

Conducted interference

 

Frequency Range0.15 MHz … 80 MHz
CommentsCriterion A
Voltage10 V (Test Level 3)

 

Conducted interference

 

Frequency Range0.15 MHz … 80 MHz
CommentsCriterion A
Voltage10 V (Test Level 3)

 

Voltage dips

 

Standards/regulations EN 61000-4-11

 

Emitted interference

 

Standards/regulations EN 61000-6-3
Radio interference voltage in acc. with EN 55011EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011EN 55011 (EN 55022) Class B, area of application: Industry and residential

 

 

TRIO-PS/1AC/24DC/20 – Power supply unit

 

Classifications

 

ECLASS

ECLASS-11.027040701
ECLASS-12.027040701
ECLASS-13.027040701

 

ETIM

ETIM 8.0EC002540

 

UNSPSC

UNSPSC 21.039121000

 

 

TRIO-PS/1AC/24DC/20 – Power supply unit

 

Environmental product compliance

 

EU RoHS

 

Fulfills EU RoHS substance requirementsYes
Exemption7(a), 7(c)-I

 

China RoHS

Environment friendly use period (EFUP)EFUP-25

 

An article-related China RoHS declaration table can be found in the download area for the respective article under “Manufacturer declaration”. For all articles with EFUP-E, no China RoHS declaration table issued and required

 

EU REACH SVHC

 

REACH candidate substance (CAS No.)Lead(CAS: 7439-92-1)
SCIP061338d1-7936-40eb-b79e-d37d0dc74e3b

 

 

 

 

 

TRIO-PS/1AC/24DC/10 – Power supply unit

 

Accessories

 

UWA 182/52 – Mounting adapter

 

Universal wall adapter for securely mounting the device in the event of strong vibrations. The device is screwed directly onto the mounting surface. The universal wall adapter is attached on the top/bottom.

 

UTA 107 – DIN rail adapter

 

Universal DIN rail adapter, for screwing on switchgear

 

TRIO-PS/1AC/24DC/20 – Power supply unit

 

PLT-SEC-T3-230-FM-UT – Type 3 surge protection device

 

Type 2/3 surge protection, consisting of protective plug and base element with screw connection. For single-phase power supply network with integrated status indicator and remote signaling. Nominal voltage: 230 V AC/DC

 

PLT-SEC-T3-24-FM-UT – Type 3 surge protection device

 

Type 3 surge protection, consisting of protective plug and base element, with integrated status indicator and remote signaling for single-phase power supply networks. Nominal voltage: 24 V AC/DC

Additional information

Weight1.1 kg
Dimensions15.2 × 11.5 × 13 cm